Title of article :
Comparison of generator circuit-breaker stresses in test laboratory and real service condition
Author/Authors :
Canay، نويسنده , , I.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Abstract :
The paper on hand shows that there may be substantial
discrepancies regarding delayed current zeros and circuitbreaker
arc energies when exposing a generator circuit-breaker to
a short-circuit in a real system or in a test lab. Depending on the
pre-loading of the generator in the real system the degree of asymmetry
may be far higher than that being adjustable in a test lab.
Based on realistic generator data the courses of the short-circuit
currents have been simulated for various cases also taking into account
the arc voltages of different circuit-breaker types. For the
same breaking current zero crossings may be delayed for several
periods and arc energies may be substantially different in the real
system compared to the test lab. Improved generator modeling is
indispensable for correct simulation of such phenomena and explains
more over “voltage depression.”
Keywords :
short-circuit currents of generators , “voltage depression”. , Circuit breaker arc energy , delayed current zero , generator circuit-breaker testing
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY