• Title of article

    36-pulse HVDC transmission for remotely sited generation

  • Author/Authors

    Villablanca، نويسنده , , M.، نويسنده , , del Valle، نويسنده , , J.، نويسنده , , Urrea، نويسنده , , C.، نويسنده , , Rojas، نويسنده , , W.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    6
  • From page
    462
  • To page
    467
  • Abstract
    Remotely sited generators that are connected to load centers may economically use HVdc transmission. The possibility of connecting the generators directly to the HVdc converter station, with both ac and dc filters removed, has been discussed frequently in the past, with significant capital and operating savings argued, but as yet without such a system being realized. It would seem that the removal of filters is not feasible. In this paper a 36-pulse operation for the converter station is proposed, whereby substantial reduction of harmonics is achieved, and thus both ac and dc filters may be removed without further implications.
  • Keywords
    HVDC Transmission , hydro electric generation. , filters , Group Connection , Harmonics , HVDC converters
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2001
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    400220