Title of article :
Verification of the short-circuit current making capability of high-voltage switching devices
Author/Authors :
Smeets، نويسنده , , R.P.P.، نويسنده , , van der Linden، نويسنده , , W.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Pages :
8
From page :
611
To page :
618
Abstract :
Switching-in of short-circuit current leads to pre-arcing in the switching device. Pre-arcing affects the ability of switchgear to close and latch. In three-phase systems, making is associated with transient voltage phenomena that may have a significant impact on the duration of the pre-arcing period. An analysis is presented of these transients. It was found that pre-arcing times in three-phase systems can be considerably prolonged with respect to a single phase situation. On the other hand, it is demonstrated that the three-phase interaction has a moderating influence on the peak value of asymmetrical current. A test-circuit is described, able to perform three-phase synthetic make tests up to 245 kV at current up to 63 kA, representing all transient phenomena. Specific tests are described requiring the maximum available laboratory power: one with a circuit breaker subjected to direct test and one with a high-speed grounding switch subjected to synthetic tests.
Keywords :
arc discharges , (AC) circuit breakers , circuitbreaker testing , switchgear testing , circuit transient analysis , short circuit currents , switching transients.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2001
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400243
Link To Document :
بازگشت