Harmonic distortion has become a main concern in
electric distribution systems during the last years. Several public
utilities are experiencing harmonic problems on their networks
and some of them started to monitor the situation of the MV and
LV distribution networks. Recently, the operation of the MV and
LV networks of the AEM—Torino (the city utility) has been investigated
with several on-site measurements. The survey led to the
observation of a step increase in voltage distortion on LV feeder
when the city street lighting is switched on and, vice versa, a sudden
decrease when it is switched off. This phenomenon can be mainly
traced back to the resonance, under certain conditions, between
the capacitance of the capacitors for the improvement of the lamps
power factor and the inductance of the MV/LV transformer. This
work investigates the phenomenon both from a theoretical point
and with laboratory and field tests. Some possible remedies and
their practical implementation to reduce harmonic distortion are
discussed.