Title of article :
Adaptive non-communication protection for power lines BO scheme 1-The delayed operation approach
Author/Authors :
Bo، نويسنده , , Z.Q. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
This paper proposes a new technique in power line
protection, the “adaptive non-communication protection.” In this
technique, protection relays make operate or restraint decisions,
adapting to system and fault conditions, without the need for communication
links. Operation without communication links to signal
the remote end relay is achieved by the detection and identification
of the operation of the circuit breaker at remote end of the
protected line section. An algorithm based on the symmetric components
is proposed to detect and identify the balance condition
of the system during the fault. The paper is focused on one of the
three protection schemes based on the new technique, the delayed
operation scheme. Simulation studies carried out for various systems
and fault conditions have demonstrated the feasibility of the
scheme.
Keywords :
BO protection , Adaptive protection , non-communicationprotection.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY