Title of article :
Adaptive non-communication protection for power lines BO scheme. II. The instant operation approach
Author/Authors :
Bo، نويسنده , , Z.Q. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
This paper presents the instant operation scheme of
the adaptive non-communication protection technique for power
lines. In the technique, protection relays make tripping or reclosure
decisions adapting to system and fault conditions without the
need for communication links. The non-communication is achieved
by the detection of whether or not the system is in a balanced operation,
in order to identify the breaker operation at the remote end
of the protected section. In the scheme, the distance relay will trip
instantly when a fault is detected outside its zone 1, but within its
zone 2 reach. Subsequently, it detects whether the fault is on the
protected section or not, and recloses when a fault is cleared from
the protected line section. Simulation studies with responses to various
system and fault condition have shown that the technique is
able to give fast and correct response without the need for a communication
link.
Keywords :
Adaptive protection , adaptive reclosure , optimal reclosure. , non-communication protection , BO protection
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY