Title of article :
Adaptive non-communication protection for power lines BO scheme 3-The accelerated operation approach
Author/Authors :
Bo، نويسنده , , Z.Q. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
This paper presents the accelerated operation scheme
of the adaptive noncommunication protection technique for power
lines with complex configurations, such as multi-end feeder and
ring main. In the scheme, the overcurrent directional relays are
arranged in two operating modes, the fixed time operation and accelerated
operation. The relays with faster operating time in the
conventional time grading coordination remain unchanged. The
new technique is employed to enable accelerated operation to be
achieved for the relays which are in the positions for which slow operating
time is set when using conventional time grading technique.
For a fault occurring on the protected system, the relays of fixed
time operation mode will operate at the preset time for the fault
within its protected direction. The relays which are programmed
to use accelerated operation mode will determine whether a fault
is on the protected section or not by using the BO technique, that is
to detect the circuit breaker operation by determining whether the
line section is in a balanced operation condition or not. The relay
makes accelerated tripping decisions for a fault on its protected
section. Simulation studies of the responses to various system and
fault conditions show that the scheme can significantly increase the
speed of the relay responses in the protection of power line systems
with complex configurations.
Keywords :
noncommunicationprotection , overcurrent directional relay. , Adaptive protection , BO protection
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :