Abstract
Determination of network harmonic impedances
using pre- and post-disturbance steady-state waveforms is a
well-known technique. Due to practical constraints, however,
it is not quite straightforward to implement the technique for
real-life applications. Using an actual utility case as an example,
this paper presents practical implementation issues involved
and their solutions. Improvements are made to the technique by
applying – –0 transformation on three-phase measurements.
The usefulness of the improved technique is demonstrated with
simulation and field measurement results. Since the technique
only requires steady-state data, it can be easily implemented with
many common power quality meters. One of the applications of
the technique is to determine the existence of resonance conditions
for shunt capacitor applications.