Title of article :
Phase-to-ground and phase-to-phase sparkover characteristics of external insulation at the entrance of a UHV substation
Author/Authors :
Yamagata، نويسنده , , Y. Oe، نويسنده , , A. Miyake، نويسنده , , K. Aihara، نويسنده , , Y. Shindo، نويسنده , , T. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
For rational insulation design of a UHV substation,
full-scale switching impulse tests of phase-to-ground (shielding
ring-to-tower) and phase-to-phase (shielding ring-to-shielding
ring) insulating clearance have been carried out in dry and wet
conditions. In the tests, shielding rings that will be installed on
bushings at actual UHVsubstations were used. The sparkover voltages
depend on not only gap configurations but also the waveform
of applied switching impulses; in other words, they show what we
refer to as -characteristics. Critical sparkover voltages are higher
than those of rod–rod gaps by 20%–25% in dry conditions and by
7%–10% in wet conditions.
Keywords :
UHVsubstations. , Air gaps , air insulation , surges , Flashover
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :