• Title of article

    BC Hydro 15 kV cable explosion

  • Author/Authors

    Abdolall، نويسنده , , K.، نويسنده , , Buchholz، نويسنده , , V.L.، نويسنده , , Cartlidge، Jonathan D. نويسنده , , D.M.، نويسنده , , Morton، نويسنده , , C.P.، نويسنده , , Armanini، Aronne نويسنده , , G.B.، نويسنده , , Harris، نويسنده , , A.، نويسنده , , Valli، نويسنده , , G.F.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    6
  • From page
    302
  • To page
    307
  • Abstract
    This investigation was prompted by a cable fault explosion inside a cable duct which housed a BC Hydro 15 kV underground standby feeder cable. The incident occurred in September 1998 at a housing complex in Vancouver, BC, Canada. Damage to the building vault was extensive and could very easily have resulted in severe injury or a fatality had anyone been in the immediate area of the vault. A failure analysis investigation revealed the cause of the explosion was an accumulation of combustible gases which were decomposition products of the polymeric cable components which were liberated from the cable by a long duration high impedance fault. Several unusual circumstances had to occur concurrently to allowthe explosive condition to develop. The events that led to the explosion are discussed in terms of the failure mechanism of the cable and the effects of reclosure arcing.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2002
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    400332