Title of article
BC Hydro 15 kV cable explosion
Author/Authors
Abdolall، نويسنده , , K.، نويسنده , , Buchholz، نويسنده , , V.L.، نويسنده , , Cartlidge، Jonathan D. نويسنده , , D.M.، نويسنده , , Morton، نويسنده , , C.P.، نويسنده , , Armanini، Aronne نويسنده , , G.B.، نويسنده , , Harris، نويسنده , , A.، نويسنده , , Valli، نويسنده , , G.F.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
6
From page
302
To page
307
Abstract
This investigation was prompted by a cable fault explosion
inside a cable duct which housed a BC Hydro 15 kV underground
standby feeder cable. The incident occurred in September
1998 at a housing complex in Vancouver, BC, Canada. Damage
to the building vault was extensive and could very easily have resulted
in severe injury or a fatality had anyone been in the immediate
area of the vault. A failure analysis investigation revealed the
cause of the explosion was an accumulation of combustible gases
which were decomposition products of the polymeric cable components
which were liberated from the cable by a long duration
high impedance fault. Several unusual circumstances had to occur
concurrently to allowthe explosive condition to develop. The events
that led to the explosion are discussed in terms of the failure mechanism
of the cable and the effects of reclosure arcing.