Title of article :
Mechanisms for degradation of TR-XLPE impulse strength during service aging
Author/Authors :
Boggs، نويسنده , , S.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
While the retained ac strength of TR-XLPE distribution
cable appears to be quite good at about 80% of the ac strength
of degassed, as-manufactured cable, the impulse strength appears
to drop linearly over time and has been reported to drop by as
much as 50% during the first two years of normal service aging before
leveling off. In this paper, we discuss the mechanisms by which
the impulse strength can degrade to a greater degree than the ac
strength. Three frequency-dependent mechanisms, which include
electrothermal, electromechanical, and electrical, have been identified.
Keywords :
XLPE. , Distribution cable , EPR , service aging , TR-XLPE
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY