Abstract
A strategy to prevent cascading outages in power systems
is proposed in this paper. The strategy employs wide-area
backup protection and artificial intelligence techniques to minimize
the impact of a fault on a network. There are two ways in
which wide-area backup protection can prevent cascading trips
leading to a wide spread blackout: 1) precise location of a fault
so that only the circuit breakers necessary to isolate the fault are
tripped and 2) avoidance of unnecessary trips, due to hidden failure
or overloading, by blocking the trip signals of conventional backup
protection relays. The limitations of conventional backup protection
are examined and methods of improvement are presented.
Keywords
Intelligent systems , hiddenfailures , wide area protection. , backup protection , cascading outages