Title of article
An analytic method for measuring accurate fundamental frequency components
Author/Authors
Soon-Ryul Nam، نويسنده , , Sang-Hee Kang، نويسنده , , Jong-Keun Park، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
7
From page
405
To page
411
Abstract
This paper proposes an analytic method for measuring
the accurate fundamental frequency component of a fault
current signal distorted with a dc-offset, a characteristic frequency
component, and harmonics. The proposed algorithm is composed
of four stages: sine filter, linear filter, Prony’s method, and
measurement. The sine filter and the linear filter eliminate harmonics
and the fundamental frequency component, respectively.
Then Prony’s method is used to estimate the parameters of the
dc-offset and the characteristic frequency component. Finally, the
fundamental frequency component is measured by compensating
the sine-filtered signal with the estimated parameters. The performance
evaluation of the proposed method is presented for a-phase
to ground faults on a 345 kV 200 km overhead transmission line.
The electromagnetic transient program (EMTP) is used to generate
fault current signals under different fault locations and fault
inception angles. It is shown that the analytic method accurately
measures the fundamental frequency component regardless of the
characteristic frequency component as well as the dc-offset.
Keywords
characteristic frequency component , Analytic method , dc-offset , Prony’s method , sine filter. , Linear filter , fundamental frequency component
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2002
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400349