• Title of article

    Modeling transformers with internal incipient faults

  • Author/Authors

    Hang Wang، نويسنده , , Butler، نويسنده , , K.L.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    10
  • From page
    500
  • To page
    509
  • Abstract
    Incipient fault detection in transformers can provide early warning of electrical failure and could prevent catastrophic losses. To develop transformer incipient fault detection technique, a transformer model to simulate internal incipient faults is required. This paper presents a methodology to model internal incipient winding faults in distribution transformers. These models were implemented by combining deteriorating insulation models with an internal short circuit fault model. The internal short circuit fault model was developed using finite element analysis. The deteriorating insulation model, including an aging model and an arcing model connected in parallel, was developed based on the physical behavior of aging insulation and the arcing phenomena occurring when the insulation was severely damaged. The characteristics of the incipient faults from the simulation were compared with those from some potential experimental incipient fault cases. The comparison showed the experimentally obtained characteristics of terminal behaviors of the faulted transformer were similar to the simulation results from the incipient fault models.
  • Keywords
    aging , Arcing , finiteelementanalysis , distribution transformer , internal incipient winding fault , modeling.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2002
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number