Title of article :
Safety aspects of GSM systems on high-voltage towers: an experimental analysis
Author/Authors :
and J. B. M. van Waes، نويسنده , , J.B.M.، نويسنده , , van Deursen، نويسنده , , A.P.J.، نويسنده , , van Riet، نويسنده , , M.J.M.، نويسنده , , Provoost، نويسنده , , F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
5
From page :
550
To page :
554
Abstract :
Low-voltage (LV) applications mounted on high-voltage (HV) towers may pose a safety problem in the low voltage network when a flashover occurs over the high-voltage insulators. To study the effects experimentally, a 150-kV system was made available. On a high voltage tower carrying a cellular phone base station, one phase insulator was shorted to the tower. A current of about 200 A was injected into that phase at a large distance. We measured the current distribution and the relevant voltages in the low voltage net. The experimental current data agree with EMTP calculations. Appropriate measures to guarantee safety for persons and electronic equipment are discussed.
Keywords :
Grounding , overvoltage , electric shocks , electricalfaults , EMC , safety , global system for mobile communication (GSM) , Transmission lines. , Distribution networks
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2002
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400371
Link To Document :
بازگشت