Title of article :
Experimental results of a supplementary technique for auto-reclosing EHV/UHV transmission lines
Author/Authors :
Eissa، نويسنده , , M.M.، نويسنده , , Malik، نويسنده , , O.P.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
A technique to discriminate between the line
charging inrush current and the current resulting on closing or
auto-reclosing a faulted EHV/UHV transmission line has been
implemented on a 32-b digital signal processor (DSP) board. The
technique is based on the voltage signals before switching and
the current signals. This technique is proposed to be a supplement
to the main protection schemes for both single-circuit and
double-circuit lines. The scheme is tested on a physical model of a
transmission system with a source at each end. Laboratory tests
show that the proposed technique is effective for three-pole and
single-pole reclosing on a faulted or healthy line.
Keywords :
Auto-reclosing , computer relaying , parallel andsingle lines , Real-time Implementation.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY