Title of article :
A novel fault-detection technique of high-impedance arcing faults in transmission lines using the wavelet transform
Author/Authors :
Chul Hwan Kim، نويسنده , , Hyun Kim، نويسنده , , Young-Hun Ko، نويسنده , , Sung-Hyun Byun، نويسنده , , Aggarwal، نويسنده , , R.K.، نويسنده , , Johns، نويسنده , , A.T.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
9
From page :
921
To page :
929
Abstract :
This paper describes a novel fault-detection technique of high-impedance faults (HIFs) in high-voltage transmission lines using the wavelet transform. Recently, the wavelet transform (WT) has been successfully applied in many fields. The technique is based on using the absolute sum value of coefficients in multiresolution signal decomposition (MSD) based on the discrete wavelet transform (DWT). A fault indicator and fault criteria are then used to detect the HIF in the transmission line. In order to discriminate between HIF and nonfault transient phenomena, such as capacitor and line switching and arc furnace loads, the concept of duration time (i.e., the transient time period), is presented. On the basis of extensive investigations, optimal mother wavelets for the detection of HIF are chosen. It is shown that the technique developed is robust to fault type, fault inception angle, fault resistance, and fault location. The paper demonstrates a new concept and methodology in HIF in transmission lines. The performance of the proposed technique is tested under a variety of fault conditions on a typical 154-kV Korean transmission-line system.
Keywords :
Fault detection , high-impedance arcing fault , Transmission Lines , wavelet transform.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2002
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400425
Link To Document :
بازگشت