Title of article :
A novel fault-detection technique of high-impedance arcing faults in transmission lines using the wavelet transform
Author/Authors :
Chul Hwan Kim، نويسنده , , Hyun Kim، نويسنده , , Young-Hun Ko، نويسنده , , Sung-Hyun Byun، نويسنده , , Aggarwal، نويسنده , , R.K.، نويسنده , , Johns، نويسنده , , A.T.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Abstract :
This paper describes a novel fault-detection
technique of high-impedance faults (HIFs) in high-voltage transmission
lines using the wavelet transform. Recently, the wavelet
transform (WT) has been successfully applied in many fields. The
technique is based on using the absolute sum value of coefficients
in multiresolution signal decomposition (MSD) based on the
discrete wavelet transform (DWT). A fault indicator and fault
criteria are then used to detect the HIF in the transmission line.
In order to discriminate between HIF and nonfault transient
phenomena, such as capacitor and line switching and arc furnace
loads, the concept of duration time (i.e., the transient time period),
is presented. On the basis of extensive investigations, optimal
mother wavelets for the detection of HIF are chosen. It is shown
that the technique developed is robust to fault type, fault inception
angle, fault resistance, and fault location. The paper demonstrates
a new concept and methodology in HIF in transmission lines. The
performance of the proposed technique is tested under a variety
of fault conditions on a typical 154-kV Korean transmission-line
system.
Keywords :
Fault detection , high-impedance arcing fault , Transmission Lines , wavelet transform.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY