Diagnostic methods in revealing internal moisture in polymer housed metal oxide surge arresters
Author/Authors
Lahti، نويسنده , , K.، نويسنده , , Kannus، نويسنده , , K.، نويسنده , , Nousiainen، نويسنده , , K.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
6
From page
951
To page
956
Abstract
Diagnostic measurements performed for surge
arresters are normally studied by evaluating their suitability
to detect aging and degradation of metal oxide material. The
suitability of different methods for revealing internal moisture in
arresters has not been studied much. This aspect is considered
in the paper based on measurement results obtained during a
1.5-yr laboratory test series conducted for six different types of
polymer-housed distribution class arresters. AC power losses,
third-harmonic content of resistive leakage current, dc leakage
current, and partial discharge measurement results over the test
period are given and discussed. Details of the measurement procedures
suitable for measuring polymeric arresters with internal
moisture are also studied. AC power loss and dc leakage current
measurements were found to be good methods, whereas the other
two can only be used as additional methods when diagnosing
internal moisture in polymer-housed arresters.
Keywords
Leak detection , Moisture , Partial discharges , Polymers. , Arresters , insulation , degradation