Thermal overload tests on a 400-MVA power transformer with a special 2.5-p.u. Short time loading capability
Author/Authors :
Nordman، نويسنده , , H.، نويسنده , , Lahtinen، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
Comprehensive load /thermal testing was performed
on a 400/400/125-MVA transformer representing a new design
generation for large power transformers with a short time
emergency loadability of 2.5 p.u. This particular overloadability
factor required special design features to control the very high
leakage flux resulting from such a loading condition and hence
ensure that the transformer satisfies existing standards limits on
hot-spot. This paper presents these design features along with a
description of a full-size transformer which was built for the sake
of developing these flux control measures. Hot-spot temperature
measurements in the windings and in the outer core packets and
structural parts under a number of overloading conditions are
presented and discussed. The results confirm the soundness of
the design to handle the 2.5-p.u. overloadability while satisfying
the hot-spot requirement according to the existing loading guides
for 1.5-p.u. overloading. The measurements also show that the
hot-spots will rise much faster than what an exponential function
based on the time constant of top oil would predict.
Keywords :
winding hot-spot. , Overloading , powertransformer , Eddy losses , leakage flux