Numerical electromagnetic field analysis of archorn voltages during a back-flashover on a 500-kV twin-circuit line
Author/Authors :
Mozumi، نويسنده , , T.، نويسنده , , Baba، نويسنده , , Y.، نويسنده , , Ishii، نويسنده , , M.، نويسنده , , Nagaoka، نويسنده , , N.، نويسنده , , Ametani، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
Archorn voltages of a simulated 500-kV twin-circuit
line, in the case of one-phase back-flashover due to lightning
to a tower top, are analyzed by the thin-wire time-domain
analysis (TWTDA) code. Prior to this analysis, a recently proposed
flashover model is incorporated into TWTDA. It becomes
clear that the archorn voltages of the other two phases show
a quite similar time-varying characteristic after one-phase
back-flashover. An EMTP simulation is also carried out. The
archorn voltages computed by the electromagnetic transients
program (EMTP) agree well with those computed by TWTDA
before the back-flashover on one phase. On the other hand,
during about 1 s after the one-phase back-flashover, the archorn
voltages of the other two phases computed by EMTP deviate
much from those computed by TWTDA. Particularly in the case
of the middle- or the lower-phase back-flashover, the deviation is
noticeable. The reason for this discrepancy is discussed.
Keywords :
Back-flashover , numerical electromagnetic fieldanalysis. , electromagnetic transients program(EMTP) , Lightning surge