Computation of very fast transient overvoltages in transformer windings
Author/Authors
Popov، نويسنده , , M.، نويسنده , , van der Sluis، نويسنده , , L.، نويسنده , , Paap، نويسنده , , G.C.، نويسنده , , De Herdt، نويسنده , , H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
7
From page
1268
To page
1274
Abstract
The paper deals with the computation of very fast
transient overvoltages (VFTOs) in transformer windings. For this
purpose, an algorithm is developed. The applied algorithm uses a
hybrid model which is a combination of the multiconductor transmission
line model (MTLM) and the single-transmission line model
(STLM). By means of the STLM, the voltages at the end of each
coil are calculated. Then, these values are used in the MTLM to
determine the distributed overvoltages along the turns. Also, this
method significantly reduces the number of linear equations that
need to be solved for each frequency to determine the required voltages
in frequency domain.
The algorithm uses a modified continuous Fourier transformation
that provides an accurate time domain computation. As an
example, the interturn voltage distributions for two 500-kV autotransformers
are computed and compared with measurements
provided by other publications.
Keywords
Fast transients , Overvoltages , transformer. , switching surges , modified Fourier transformation