• Title of article

    A new method for the calculation of the hot-spot temperature in power transformers with ONAN cooling

  • Author/Authors

    Radakovic، نويسنده , , Z.، نويسنده , , Feser، نويسنده , , K.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    9
  • From page
    1284
  • To page
    1292
  • Abstract
    In the previous work of the authors, an original thermal model of transformers with ONAN cooling was developed. The model takes into account the influence of nonlinear thermal characteristics in transient thermal processes; instead of exponential functions and time constants, the numerical solution of differential equations is used. The model delivers one characteristic temperature in copper (solid insulation) and one characteristic temperature in oil. In this paper, the analysis stresses the definition of the hot-spot temperature of the solid insulation by using easily measurable quantities. Then, the parameters of the model can be precisely determined from inexpensive measurements in a short-circuit heating experiment and the model can deliver the hot-spot temperature. The experimental base of this research are the measurements on a 630-kVA, 3 10 kV 3 6 kV ONAN transformer equipped with 112 temperature sensors (102 inside the central positioned 10-kV winding).
  • Keywords
    Thermal modeling. , power transformerthermal factors , Hot-spot temperature
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number