Abstract
In the previous work of the authors, an original
thermal model of transformers with ONAN cooling was developed.
The model takes into account the influence of nonlinear
thermal characteristics in transient thermal processes; instead
of exponential functions and time constants, the numerical
solution of differential equations is used. The model delivers
one characteristic temperature in copper (solid insulation) and
one characteristic temperature in oil. In this paper, the analysis
stresses the definition of the hot-spot temperature of the
solid insulation by using easily measurable quantities. Then,
the parameters of the model can be precisely determined from
inexpensive measurements in a short-circuit heating experiment
and the model can deliver the hot-spot temperature. The experimental
base of this research are the measurements on a 630-kVA,
3 10 kV 3 6 kV ONAN transformer equipped with 112
temperature sensors (102 inside the central positioned 10-kV
winding).
Keywords
Thermal modeling. , power transformerthermal factors , Hot-spot temperature