Title of article :
The influence of personal computer processing modes on line current harmonics
Author/Authors :
Moore، نويسنده , , P.J.، نويسنده , , Portugues، نويسنده , , I.E.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
The influence of the personal computer processing
mode on the generation of line current harmonics has been
investigated using a university library building containing over
370 PCs. The harmonics were monitored from the building
switchboard using purpose-designed hardware. The PCs were
set to execute four types of processing mode: idle, numerical
processing, floppy, and hard disk accesses. The results recorded
were indicative of harmonics caused by the PC box only; secondary
effects of harmonic production caused by distorted supply
voltages were avoided. The results show that hard disk accesses
cause the highest level of harmonic production affecting the 3rd
and 5th components. Harmonic attenuation was very apparent
when comparing the results between a single PC and 124 PCs
connected to the same supply phase. However, attenuation and
diversity effects due to changes in loading level on the PC power
supply were not as predicted, showing an increase in harmonic
generation with line current rms level.
Keywords :
harmonicdiversity , harmonic attenuation , power quality , Data processing , line currents , switched mode power supplies. , Personal computers
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :