Title of article :
Diagnosis of Moisture in Oil/Paper Distribution Cables—Part II: Water Penetration in Cable Insulation–Experiment and
Modeling
Author/Authors :
R. Neimanis، نويسنده , , R. Eriksson، نويسنده , , and R. Papazyan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
Dynamics of water penetration in mass impregnated
cable insulation has been studied. For experimental purposes, artificial
damage has been inflicted to a 40-cm-long cable sample and
water ingress has been continuously monitored by frequency response
measurements. A similar experiment has been conducted
on 2.8-m-long cable sample, where both frequency response and
time-domain reflectometry (TDR) measurements have been performed.
After termination of both experiments, actual moisture
content has been measured radially and axially. Based on dielectric
measurements, a model of water ingress has been developed and
diffusion coefficients have been estimated for mass impregnated
cable paper.
Keywords :
massimpregnated cable , oil paper insulation. , moisture content , Karl Fischer titration , Dielectric response
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY