Title of article :
Deriving the Signal-to-Noise Ratio Probability of Error and Performance Measure Matrices for Distribution Line Carrier
Signals Propagation (Using Bus Impedance Approach)
Author/Authors :
F. K. Amoura and W. S. Abu-Elhaija، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
The automated distribution system using distribution
line carrier (DLC) needs a two way communication between the
various controlled terminals and the main substation. Digital data
should be transmitted over the distribution power lines from the
main substation to the transceivers in the distribution system and
vice versa. The distribution system is a hostile medium for data
transmission [i.e., high noise levels and standing wave patterns with
low voltage nodes (as a result of signal reflections in the system)].
This hostility leads to low signal-to-noise ratio (SNR) locations and
subsequently to high probability of bit error at these locations.
The bus impedance matrix was developed for medium voltage
distribution system. An actual medium voltage distribution line
was tested. The actual measurements of the tested line verified the
validity of the derived equations. The above mentioned line with
the addition of a branch is used as an example in this paper. This
paper derives (SNR) probability of bit error and performance measure
transfer rate of information bits (TRIB) matrices of any DLC
system starting from the bus impedance matrix.
Keywords :
signal-to-noise ratio. , Bus impedance matrix , distribution line carriersystem
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY