Title of article
Effects of Hot on Post-Arc Circuit Breaker Design
Author/Authors
T. Uchii، نويسنده , , S. Nishiwaki، نويسنده , , and S. Boggs، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
7
From page
124
To page
130
Abstract
SF6 is blown through the arc during interruption of
an SF6 puffer circuit breaker. This hot gas flows down an exhaust
tube into the chamber of a dead tank circuit breaker where it can
lower the dielectric withstand between the exhaust tube and the
tank of the circuit breaker, leading to dielectric breakdown during
the transient recovery voltage after clearing. This paper presents
experimental evidence that any such breakdown is controlled by
the hot gas near the exhaust tube, with cold gas in the remainder
of gap having little effect on the breakdown voltage. This experimental
conclusion is supported by a detailed theory for conditions
under which breakdown can occur.
Keywords
transient recoveryvoltage. , gas circuit breaker , SF6 , ARC
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2004
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400567
Link To Document