Title of article :
Real-Time Measurement Approach for Tracking the Actual Coefficient of of Electric Arc Furnace
Author/Authors :
J.-L. Guan، نويسنده , , J.-C. Gu، نويسنده , , and C.-J. Wu، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
7
From page :
309
To page :
315
Abstract :
This investigation develops a new definition of the voltage fluctuation ( ) electric arc furnace. Analysis of voltage flicker spectrum in the 0.25–30-Hz range reveals that the magnitude of each modulation frequency component decreases with frequency, while the standard deviation of each frequency component is high. From the statistics of electric arc furnace real time test data, the loads can be classified as weakly stationary processes, but lack a Gauss probability distribution. Traditionally, the equivalent 10-Hz voltage fluctuation ( 10) value can be obtained from 3 6. However, the real world tests and statistics indicate that the ratios of 10 are 1.8, not 3.6.
Keywords :
Flicker , voltage fluctuation. , Arc furnace
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400593
Link To Document :
بازگشت