Title of article
False Operation of Vector Surge Relays
Author/Authors
W. Freitas and W. Xu، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
3
From page
436
To page
438
Abstract
This paper presents an investigation about false
operation of vector surge relays due to adjacent feeder faults.
The objective was to explore the scenarios that led to a higher
risk of false operation. Simulation results have shown that the
main factors affecting false operation are system and generator
loading, generator inertia constant, amount of power exported
by the generator, short-circuit level, feeder X R ratio, fault
clearance time, and electrical distance between the generator
and the fault.
Keywords
Distributed generation , false operation , islandingdetection , Synchronous generators , vector surge relays.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2004
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400612