Title of article :
Fault Location in Transmission Lines Using One-Terminal Postfault Voltage Data
Author/Authors :
C. E. M. Pereira and L. C. Zanetta، نويسنده , , Jr.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
A new algorithm for fault location in transmission
lines, with fault distance calculation based on steady-state measured
phasors in local terminal is presented. For the postfault, only
voltage phasors are required, avoiding possible errors due to current
transformer saturation; the current phasors are required only
in prefault time, when saturation does not occur. The algorithm
does not use simplifying hypothesis but requires system equivalent
data at both line terminals and the fault classification, considering
fault resistance purely resistive.
In order to verify the algorithm performance, a parametric
analysis of variables that influences short-circuit conditions is
developed, including an analysis of remote equivalent setting.
The results show that the algorithm is very accurate, even in
cases when the remote equivalent is not well fitted.
Keywords :
fault location. , EHV transmission lines , Fault diagnosis , Distance measurement
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY