Title of article :
Fault Location in Transmission Lines Using One-Terminal Postfault Voltage Data
Author/Authors :
C. E. M. Pereira and L. C. Zanetta، نويسنده , , Jr.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
6
From page :
570
To page :
575
Abstract :
A new algorithm for fault location in transmission lines, with fault distance calculation based on steady-state measured phasors in local terminal is presented. For the postfault, only voltage phasors are required, avoiding possible errors due to current transformer saturation; the current phasors are required only in prefault time, when saturation does not occur. The algorithm does not use simplifying hypothesis but requires system equivalent data at both line terminals and the fault classification, considering fault resistance purely resistive. In order to verify the algorithm performance, a parametric analysis of variables that influences short-circuit conditions is developed, including an analysis of remote equivalent setting. The results show that the algorithm is very accurate, even in cases when the remote equivalent is not well fitted.
Keywords :
fault location. , EHV transmission lines , Fault diagnosis , Distance measurement
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400631
Link To Document :
بازگشت