Title of article :
A New Concept of Voltage-Collapse Protection Based on Local Phasors
Author/Authors :
G. Verbic? and F. Gubina، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
6
From page :
576
To page :
581
Abstract :
A new algorithm for protection against voltage collapse is proposed. The algorithm makes use of the magnitudes and angles of the local phasors (i.e., bus voltages and load currents). The change in an apparent power-line flow during a time interval is exploited for computing the voltage-collapse criterion. The criterion is based on the fact that the line losses in the vicinity of the voltage collapse increase faster than the delivery of the apparent power and, at the voltage-collapse point, the losses consume all of the increased power. The selected criterion equals 0 when a voltage collapse occurs. The proposed algorithm could be easily implemented in a numerical relay. The information obtained by the relay can be used at two levels–for the coordinated system-wide control action or for automatic action on the local level. The algorithm is simple and computationally very fast. It was tested on the IEEE 118-bus test system.
Keywords :
Power System Protection , voltage collapse. , Power System Dynamic Stability , Local phasors
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2004
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400632
Link To Document :
بازگشت