Title of article :
A New Concept of Voltage-Collapse Protection Based on Local Phasors
Author/Authors :
G. Verbic? and F. Gubina، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
A new algorithm for protection against voltage collapse
is proposed. The algorithm makes use of the magnitudes and
angles of the local phasors (i.e., bus voltages and load currents).
The change in an apparent power-line flow during a time interval
is exploited for computing the voltage-collapse criterion. The criterion
is based on the fact that the line losses in the vicinity of the
voltage collapse increase faster than the delivery of the apparent
power and, at the voltage-collapse point, the losses consume all of
the increased power. The selected criterion equals 0 when a voltage
collapse occurs.
The proposed algorithm could be easily implemented in a numerical
relay. The information obtained by the relay can be used
at two levels–for the coordinated system-wide control action or for
automatic action on the local level.
The algorithm is simple and computationally very fast. It was
tested on the IEEE 118-bus test system.
Keywords :
Power System Protection , voltage collapse. , Power System Dynamic Stability , Local phasors
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :