Title of article :
Condition Assessment of Contacts in Gas-Insulated Substations
Author/Authors :
M. Runde، نويسنده , , O. Lillevik، نويسنده , , Helge V. Larsen، نويسنده , , B. Skyberg، نويسنده , , A. Mjelve، نويسنده , , and A. Tonstad، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
A new method for assessing the condition of electric
contacts and joints inside gas-insulated substations (GISs) that
overcomes the limitations of conventional diagnostic methods is
proposed. The contact resistance in degraded or overstressed electrical
contacts varies slightly when currents of different amplitudes
are passed. The diagnostic method is based on detecting this nonlinear
behavior. For testing of the contacts in large GIS, excitation
currents up to several thousand amperes are required. By using a
capacitor-based current supply, such currents can be achieved with
a portable source. The testing can be carried out without dismantling
the GIS. No earlier measurements or manufacturer specifications
are required. In full-scale testing under realistic operating
conditions on 145–420 kV GIS using prototype instrumentation a
very good sensitivity for detecting contact degradation in an early
stage was obtained.
Keywords :
contact resistance , contacts , Fault diagnosis , gasinsulatedsubstations , testing. , Test equipment
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY