Title of article
Optimizing Transmission Path Utilization in Idaho Power
Author/Authors
O. A. Ciniglio and A. K. Deb، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
5
From page
830
To page
834
Abstract
A new line current profile based dynamic line rating
system has been implemented at Idaho Power Company by
real-time exchange of data with Energy Management System and
real-time weather data from the Internet. Increased utilization of
transmission critical path is made possible by wide-area real-time
dynamic rating using Internet based weather data. Economic
analysis shows significant benefit of operating transmission lines
at higher ratings by taking advantage of favorable weather
conditions during overload conditions. A case study of an internal
transmission interface including the Brownlee East path in Idaho
Power using the new dynamic line rating system and an associated
overload mitigation system is presented. It is shown there is
minimum risk of overloading a circuit by increased transmission
path utilization under N-1 contingency conditions.
Keywords
Dynamic thermal rating , line ampacity , powertransmission control , power transmission lines.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2004
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400665
Link To Document