Title of article :
Arc Effect on Single-Phase Reclosing Time of a UHV Power Transmission Line
Author/Authors :
I. M. Dudurych، نويسنده , , T. J. Gallagher، نويسنده , , and E. Rosolowski، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
One of the important operational conditions of a
single-circuit ultra-high-voltage transmission line is the power
transmission by two phases during the clearance of a temporary
single-phase short circuit. Such a condition may be sustained
for an interval of 1 s without losing the dynamic stability of the
system. The influence of the arc on the single-phase reclosing
time of an ultra-high-voltage power transmission line is investigated
on the basis of the primary and the secondary arc models
incorporated into the transient program EMTP. The validity of
the models used is proven by comparison with field test results
on an actual 1150-kV power transmission line from Ekibastuz to
Kokchetav in Northern Kazakhstan. The processes of this power
transmission in the “dead time” of the single-phase reclosing
cycle are simulated. It is shown in the paper that simplified
short-circuit simulation without the incorporation of the dynamic
arc model leads to erroneous results. Mathematical analysis and
field experiments show that natural secondary arc extinguishing
in a highly compensated 1150-kV power transmission line cannot
be reached in a reasonable time (e.g., less than 1 s). It is shown
in the paper that this problem can be solved by automatic phase
shunting (APS) of the faulted phase.
Keywords :
Arc discharges , modeling , reclosing devices , transientanalysis , UHV transmission.