• Title of article

    Digital Correction Method for an H-Field Sensor in Power System EMC Measurements

  • Author/Authors

    Q. Li، نويسنده , , W. H. Siew، نويسنده , , M. G. Stewart، نويسنده , , P. Wang and S. K. Walker، نويسنده , , and C. Piner، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    5
  • From page
    952
  • To page
    956
  • Abstract
    Analysis was conducted on the nature and characteristics of an -field sensor for power system electromagnetic compatibility (EMC) measurements. Based on the original calibrated response curve of the magnetic-field ( ) sensor and steepest descent theory, an analog model has been created to represent the sensor’s transfer function. This function was converted into a set of digital algorithms by the bilinear transformation method, thus allowing subsequent signal processing on available software. The digital correction model for the sensor gives an estimated error of within 8% for all the relevant frequency components. The results present some general analysis methods for power system EMC measurements.
  • Keywords
    steepest descentalgorithms. , digital modeling , EMCmeasurement
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2004
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number