Title of article
Modal Analysis of Industrial System Harmonics Using the s-Domain Approach
Author/Authors
S. L. Varricchio، نويسنده , , S. Gomes Jr.، نويسنده , , N. Martins، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
6
From page
1232
To page
1237
Abstract
This paper describes the use of modal analysis of
s-domain network models in the solution of harmonic distortion
problems of industrial systems. Modal analysis involves the
computation of the system poles, transfer function zeros as well
as their sensitivities to changes in network parameters. A new
modal sensitivity coefficient and a new modal observability index
are introduced. These new coefficient and index are used to
solve harmonic problems in a practical industrial system having
multiple harmonic sources. The results obtained are believed to
demonstrate the practical value of the proposed method.
Keywords
Harmonics , sensitivitycoefficients. , power quality , Modal analysis
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY