Abstract
The installed transformer capacity can be reduced
when the transformer connects intermittent loads with low duty
cycles. This paper proposes a new method based on genetic algorithms
to determine the transformer capacities for intermittent
loads. The costs of transformers are minimized while the voltage
fluctuations (drops) satisfy relevant standards. The duration of the
voltage drop can be derived from the Markov Process. The intermittent
loads are modeled with discrete stochastic distribution;
therefore, the generating function is used for aggregating multi-intermittent
loads at a bus. Two practical factories with grinders and
welders are used to show the applicability of the proposed method.
Keywords
Markov process , transformer capacity. , Discrete random variable , intermittentload , Genetic algorithms