Title of article :
Problems of Voltage Transducer in Harmonic Measurement
Author/Authors :
Y. Xiao، نويسنده , , J. Fu، نويسنده , , B. Hu، نويسنده , , X. Li، نويسنده , , and C. Deng، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
5
From page :
1483
To page :
1487
Abstract :
If the neutral point either on primary or secondary side of potential transformer is not grounded directly, the harmonic voltage measurement will not reflect the real distortion of the system voltage. Also, capacitive voltage transformer on high and medium voltage system cannot be used for harmonic voltage measurement. A new method to set the voltage signal from the tap of Current Transformer bushing is recommended here. The recommended method can achieve a more precise result of harmonic voltage measurement.
Keywords :
potential transformer , power system harmonics , voltagetransducer. , Capacitive voltage transformer , harmonic measurement