Abstract :
This paper clarifies the operating principles of a
controllable reactor of transformer type (CRT). In nature, a
CRT is equivalent to a multi-winding transformer for which the
low-voltage windings (control windings) operate at short-circuited
states in turn. This kind of reactor possesses such advantages as
smooth power regulation, low current harmonic content, and fast
response. Taking account of the coupling of the control windings,
this paper examined the current harmonic content for the
work winding by Fourier series decomposition, and thus derived
the current harmonic coefficients. Based on the solution of the
branch current equation of a multi-winding transformer, and
introduction of the concept of equivalent winding impedance, a
polygon-type equivalent circuit is proposed for a multi-winding
transformer. Subsequently, formulae for the branch impedances
of the equivalent circuit are presented. According to the harmonic
content constraints, the number of control steps is determined.
Then, by combining the MMF and branch current equations, an
expanded equation about the winding currents and current-limiting
reactances is obtained. According to the feature that the
control windings are short-circuited in turn, the current-limiting
reactances are calculated for each control winding step by step. At
last, based on the proposed equivalent circuit for a multi-winding
transformer, a simulation model for a CRT is fabricated with
MATLAB/SIMULINK/PSB. The simulation results confirmed the
presented work, which underpins the further analysis and design
of a CRT.
Keywords :
simulation , transformertype. , current-limiting reactor , Controllable reactor , equivalent circuit , harmonics analysis