• Title of article

    Research on Insulation Design of 22.9-kV High- Superconducting Cable in Korea

  • Author/Authors

    Y.-S. Kim، نويسنده , , D.-S. Kwag، نويسنده , , H.-J. Kim، نويسنده , , J.-W. Cho، نويسنده , , K.-C. Seong، نويسنده , , and S.-H. Kim، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    6
  • From page
    554
  • To page
    559
  • Abstract
    The electrical insulation design is important for high-Tc superconducting (HTS) cable because the cable is operated in a medium voltage environment. For the insulation design of HTS cable, it is necessary to investigate the ac, impulse breakdown, and partial discharge inception stress of a liquid nitrogen/polypropylene laminated paper composite insulation system. These results were used to design the electrical insulation of 22.9-kV-class HTS cable in Korea and cable was manufactured. A manufactured mini-model HTS cable was evaluated for ac withstand voltage, impulse withstand voltage, breakdown and dielectric tangent loss (tan ). From these tests, the cable has satisfied the standard technical specification of KEPCO in Korea. The breakdown voltage was 110 kV.
  • Keywords
    AC withstand voltage , dielectric tangent loss , high-Tc superconducting (HTS) cable , partial discharge inceptionstress.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2005
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number