Title of article :
Numeral Analysis Model for Shielding Failure of Transmission Line Under Lightning Stroke
Author/Authors :
J. He، نويسنده , , Y. Tu، نويسنده , , R. R. Zeng and M. Wei، نويسنده , , J. B. Lee، نويسنده , , S. H. Chang، نويسنده , , Z. Guan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
The shielding failure is the occurrence of a lightning
stroke that bypasses the overhead ground wires and terminates on
the phase conductors. The correct design to improve the shielding
effect of transmission line to lightning is one of the key problems of
transmission line design. A numerical analysis model for shielding
failure of transmission line based on electromagnetic field theory is
proposed in this paper. The electrical field of the system including
lightning leader, transmission line and ground is solved, the range
of lightning current striking the phase conductor is obtained, and
the shielding failure probability of transmission line is calculated.
The lightning leader model and the critical breakdown electrical
field intensity of long gap are discussed. The analyzed results by
numerical analysis model are compared with those by the electrogeometric
model.
Keywords :
electricalfield , lightning leader , Electrogeometric model , Shielding failure , transmission line. , Critical breakdown electrical field , numerical analysismodel
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY