Abstract :
This paper presents a procedure for calculating the
maximum lightning overvoltage along a cable which is protected
by arresters at both ends. It is shown that the most severe cable
overvoltages that can occur (close back-flashover) will appear at a
distance from the remote cable end which is in the order of some
hundred meters. The maximum voltage is calculated by adding
the peak value of the voltage wave in the forward direction and
the peak value of the voltage wave in the backward direction. The
location of the maximum voltage is obtained by considering the
difference in time instants at which the peak value occurs at the
remote end. This procedure only requires to calculate the voltage
at the cable ends and the surge arrester current. The forward and
backward waves can then be calculated by simple expressions. The
procedure is demonstrated for a 300 kV system, for different cable
lengths.