Abstract
In contrast to most other power-quality phenomena,
it requires several years of measurements to obtain a good insight
of the voltage sag problems at a given grid connection point. In
some countries, sag measurements at high- or medium-voltage
level of several years are available. This paper analyzes how to
calculate the sag characteristics at lower voltage levels if the sags
measured at higher voltage levels are only characterized as the
largest value of the voltage drop in each phase. Whether these
values are based on phase-to-phase or phase-to-neutral voltages
turns out to be an important parameter and is therefore analyzed
in detail. Based on this analysis, this paper gives guidelines on
how new sag meters should preferably be connected (measuring
phase-to-phase or phase-to-neutral voltages).