A Moisture-in-Oil Model for Power Transformer Monitoring—Part II: Experimental Verification
Author/Authors
B. Garc?a، نويسنده , , J. C. Burgos، نويسنده , , ?. M. Alonso، نويسنده , , J. Sanz، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
7
From page
1423
To page
1429
Abstract
In the companion paper, a model to detect failures
leading to an increase of the water content in transformer oil was
proposed. In this paper, the experimental verification of the Model
is presented. The Model was tested in a 1500-kVA test transformer
constructed as a reduced scale model of a 60-MVA 220-kV transformer.
In order to load the Transformer to have the capability of
varying load and power factor over a wide range, the opposition
method described in IEC 60076-2 Standard was used. Sensors to
measure temperature and moisture in oil were installed in the Test
Transformer. The Model was adjusted and validated using a set of
data corresponding to different operating conditions. The Transformer
was submitted to an accelerated aging process studying the
Model response in such a case. In order to verify the Model’s ability
to detect failures, a water ingress in the Transformer was simulated.
Keywords
Moisture , monitoring , oil insulation , paper insulation , Power Transformers , power transformer insulation testing.