Title of article
Radiated Emissions From FACTS Equipment Operational Within Substations—Part III
Author/Authors
Q. Li، نويسنده , , W. H. Siew، نويسنده , , M. G. Stewart، نويسنده , , P. Wang and S. K. Walker، نويسنده , , and C. Piner، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
9
From page
1788
To page
1796
Abstract
Transient electromagnetic (EM) emissions are generated
when thyristor or gate turn-off thyristor (GTO) valves
are being switched on and off within substations installed with
static var compensators (SVCs) and static synchronous compensators
(STATCOMs). These emissions may cause malfunction of,
or damage to, electronic equipment positioned nearby without
appropriate protection. Four SVC-based substations and one
STATCOM-based substation were selected for electromagneticinterference
(EMI) measurement, analysis, and evaluation. A
comparison was made between the radiated EMI features from
each. The analyzed results were correlated to the present electromagnetic-
compatibility standards, and recommendations of
changes for immunity tests were presented specifically for flexible
ac transmission system (FACTS)-based radiated EMI. Preliminary
analysis was also given to the causes of FACTS-based EMI,
which indicated that valve switching behavior and the stray parameters
of FACTS equipment layout were the main contributors
to high-frequency-radiated interference.