• Title of article

    Effect of Puffer Volume and Operating Force on Dielectric Recovery Performance in Thermal Puffer-Type Gas Circuit Breaker

  • Author/Authors

    N. Osawa and Y. Yoshioka، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    7
  • From page
    1897
  • To page
    1903
  • Abstract
    In order to investigate the influence of puffer volume and operating force to dielectric performance of GCB at current interruption, we calculated the prospective dielectric withstand voltage between arcing contacts. The withstand voltage was calculated by the electric field strength appeared on arcing contacts and the allowable electric field strength of hot gas due to thermal puffer action. We could clarify that large initial puffer volume can increase withstand voltage at current breaking point and also that an optimum point exists in operating force . For example, it was found that in case of the operating force of 1000 kgf, the puffer volume of 1.2 liter would be best choice in the interrupting condition of = 50kAand arcing time of 1.35 cycle.
  • Keywords
    gascircuit breakers , Electric field analysis and gas flow analysis , thermal puffer , withstand voltage.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2005
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    400956