Title of article :
Method to observe the change of charges in an electric double layer between pressboard and the insulating oil in a power transformer
Author/Authors :
Huh ، نويسنده , , C.-S.; Jeong، نويسنده , , J.-I.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
Space charge is one of the important causes of electrical breakdown. It has been necessary
to sample the oil in an oil-cooling transformer to establish how charged it is. A method to detect the
change in accumulated charges on a pressboard in an oil transformer is suggested. The change in the
level of charge relates to the charges in the oil, so the charges in oil and on a pressboard can be
observed without sampling the oil by using this method. An electrometer, a high input impedance
voltage meter, and an oil circulation system were used to detect the change. When the oil went
through the pressboard pipe, it was charged positively due to the streaming electrification. The
voltage change on the surface of the pressboard was measured by a high input impedance voltmeter
and the current from the surface by a micro-ammeter. From these data, the change in static charge is
known.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications