Title of article :
Continuous conduction mode operation of three-phase diode bridge rectifier with constant load voltage
Author/Authors :
Bleijs، نويسنده , , J.A.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Abstract :
Three-phase diode bridge rectifiers with a low source reactance cause considerable
current harmonics in the AC supply, which may not meet the latest EMI regulations. At higher
source reactance the bridge is more likely to operate in continuous conduction mode (CCM),
leading to a reduction in harmonic current level. In the paper accurate analytical expressions are
derived for the AC current harmonics, the input power and the power factor in CCM, which have
been validated through numerical simulations and practical experiments. They can therefore be
used with confidence for the design of power supplies with lower harmonic levels. Remedies are
proposed to compensate for the drawbacks of CCM operation, using power factor correction
capacitors and a single-switch inductor-less boost rectifier.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications