Title of article
Safety assessment of AC earthing systems in a DC traction-supply substation
Author/Authors
Lee، نويسنده , , C.-H.; Lin، نويسنده , , S.-D.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
9
From page
885
To page
893
Abstract
The paper assesses safety of AC earthing systems in a DC traction-supply substation
(TSS) by comparing the designed mesh and step voltages to the maximum tolerable voltages.
Generally, IEEE 80 criteria are based on the maximum tolerable body current to prevent
fibrillation of the human heart, and this current is then translated into tolerable touch and step
voltages. As a result, safety assessment of AC earthing systems in a DC TSS is referred to a
procedure by which the designed mesh and step voltages are computed and compared with the
tolerable touch and step voltages. Computation results of AC earthing systems for the orange line
at O19 TSS in Taipei rapid-transit systems are presented as an example.