Abstract
An optimisation criterion is presented which allows proper calculation of optimum fixed
LC combination in a power factor installation. Optimisation maximises the harmonic-adjusted
power factor. In the paper, it is assumed that the load harmonics are not sufficiently serious to
suggest tuned filters, but, when combined with source harmonics, the use of a pure capacitive
compensator would degrade power factor and overload equipment. Consequently, an LC
compensator is selected. It appears that this approach is practical, justifiable, compatible with
existing rate structures and relatively easy to implement. The contribution of the developed method
is demonstrated in examples taken from previous publications.