Title of article :
Harmonic adjusted power factor correction in nonsinusoidal environment
Author/Authors :
Zobaa، نويسنده , , A.F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
7
From page :
960
To page :
966
Abstract :
An optimisation criterion is presented which allows proper calculation of optimum fixed LC combination in a power factor installation. Optimisation maximises the harmonic-adjusted power factor. In the paper, it is assumed that the load harmonics are not sufficiently serious to suggest tuned filters, but, when combined with source harmonics, the use of a pure capacitive compensator would degrade power factor and overload equipment. Consequently, an LC compensator is selected. It appears that this approach is practical, justifiable, compatible with existing rate structures and relatively easy to implement. The contribution of the developed method is demonstrated in examples taken from previous publications.
Journal title :
IEE Proceedings Electric Power Applications
Serial Year :
2005
Journal title :
IEE Proceedings Electric Power Applications
Record number :
402835
Link To Document :
بازگشت