Title of article :
Performance and mathematical model of threephase three-winding transformer used in 2 x 25kV electric railway
Author/Authors :
Mingli، نويسنده , , W.; Chengshan، نويسنده , , X.; Fan، نويسنده , , Y.; Zheng، نويسنده , , T.Q.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2006
Abstract :
A three-phase three-winding transformer, the so-called cross-connected transformer, has
been used in a 2* 25kV electric railway in China. Based on the magnetomotive force balance
equations, winding connection equations, output-port equations and voltage transfer equations,
the performance and mathematical model of the cross-connected transformer are analysed. The
input current and output voltage equations and nodal admittance matrix of the transformer
are obtained, which can be used in future analyses. The problem of omitting substation
autotransformers is addressed by virtue of two equivalent circuits put forward. The applicability of
the proposed formulas and mathematical model is validated by comparison of measured and
calculated busbar voltages and short-circuit simulations. Finally, the reasons that led to the low
catenary voltage of one section of the Datong–Qinghuangdao railway, supplied by a crossconnected
transformer, are investigated.
Journal title :
IEE Proceedings Electric Power Applications
Journal title :
IEE Proceedings Electric Power Applications